Aerotech Fans
Loading industrial-grade components...

Dual-purpose fan designed for normal kitchen exhaust ventilation and emergency high-temperature smoke spill operation. Certified to withstand 300°C or 400°C for 2 hours, ensuring safe evacuation paths in the event of a commercial kitchen fire.
Max Airflow
Up to 80,000 CMH
Max Temp
300°C or 400°C for 2 hours
Material
Mild Steel casing with high-temp paint
Drive Type
Direct Drive (Class H Motor)
Automatic Activation
Triggers upon fire alarm for immediate response
High Temperature Operation
Functional at 250–300°C for 2+ hours
Dual Purpose
Used for normal ventilation and emergency smoke extraction
Energy Efficient
Designed to minimize operational costs
Kitchen & Food
Commercial
Industrial
| Model | Air Volume (CFM) | Static Pressure (in.wg) | RPM (Max) | Motor (HP) |
|---|---|---|---|---|
| KSS-600 | 10,000 | 250 | 1,440 | 5 |
| KSS-900 | 25,000 | 450 | 1,440 | 15 |
| KSS-1250 | 47,000 | 700 | 960 | 30 |
Certified commercial smoke spill fans are engineered with Class H motor insulation to operate continuously for either 2 hours at 250°C, or 2 hours at 400°C, depending on the specific local fire-code compliance and building life-safety requirements.
In a fire emergency, preserving human life by maintaining a smoke-free escape route supersedes protecting the equipment. Smoke spill motors are hardwired to bypass all VFDs and thermal overload relays, intentionally running the motor to destruction rather than tripping and allowing the building to fill with toxic smoke.